Diesel generator set installation site specific requirements are summarized as follows:
1, Diesel generator set installation site must be well-ventilated, the generator terminal should be enough air inlet, diesel engine should be a good outlet end. Vent area should be more than 1.5 times greater than the water tank area.
2, Around the diesel generator set is installed should be kept clean and to avoid produce acidic, alkaline and corrosive gases and steam items placed in the vicinity. Conditional fire extinguishing devices should be configured.
3, For indoor use, it must be through guided outdoor exhaust pipes, pipe diameter must be ≥ muffler out smoke pipe diameter, connected piping elbow should not be more than 3 to ensure the smooth flow of smoke, and should pipe down tilt 5-10 degrees, avoid rain water injection; must be retrofitted rain cover if the exhaust pipe installed vertically upwards.
4, Diesel generator set enclosure must have reliable protection grounding the generator neutral grounding, must be carried out by professionals neutral ground, and configure the lightning protection devices, non-mains earthing the neutral point directly to ground. The two-way switch with the mains must be very reliable, to prevent inverted power transmission. Two-way switch wiring reliability and subject to inspection and approval of the local power supply department.
5, The old section of the diesel generator sets requires the use of concrete as a foundation, installation foot level measured level fixed on the basis of the level of the unit. Between the unit and the foundation should be dedicated shockproof pad or foot bolts. Modern diesel generator does not require a concrete foundation, modern diesel generating set has been improved, and the entire unit ground is flat, and are equipped with a shock absorber, very convenient.